There continues to be a great deal of activity surrounding the update to NFPA 70E scheduled to be published in October 2008. For the proposed 2008 edition of NFPA 70, National Electrical Code® (NEC®), the Technical Correlating Committee (TCC) received 3,668 proposals and 3,206 comments during the revision cycle. For those of us involved in working with energized electrical circuits the outcome of the new standards will likely impact how we do our job. The goal is to increase safety through well thought through practices.
How are Thermographers Addressing the Issue?
Increasing the distance at which inspections of open cabinets are performed.
Most cameras offer telephoto lens that enable the thermographer to stand 2 to 3 times further away from the energized components while maintaining the same resolution. In addition newer high definition cameras will provide the same performance as 320x240 array based cameras at twice the normal standoff.
New Language Being Drafted by NFPA and ASTM
ASTM E-1934
New language is being proposed in the next version of ASTM E-1934, Standard of Examining Electrical Power Distribution Equipment with Infrared Technology. 7.5 - As an alternative, consideration may be given to conducting the examination through "windows" that are transparent to detected infrared radiation or to "ports." Safety procedures should be modified to accommodate this task. Care must be taken to insure that all equipment can be seen and special lenses may be required.
Did You Know?
Incident energy from an arc flash created with vertical, unterminated conductors in a cabinet (20" x 20" x 20") decreases by the inverse of the distance to the 1.5 power. If the arc has horizontal conductors that point out of the cabinet opening or vertical which terminate into an insulated barrier, the exposure may decrease by a lower exponent, but not enough data has been collected on these conductor configurations. - Tom Neal of Neal Associates
Next Revision of NFPA 70E
The following new language has been submitted to, and is being considered, by the 70E committee: "When access to conduct such inspections of energized equipment is limited by the appropriate use of special windows or small access ports, rather than by gaining access though opening the enclosure door, the limit of the approach, and the required PPE, will be the same as if the enclosure door were left unopened."
Increased diligence of OSHA
Although it is only referenced in OSHA 29 CFR Part 1910 Subpart S, Appendix A, NFPA 70E is considered by OSHA to be the recognized industry practice for electrical safety.
Role of NFPA
OSHA standards don't provide details on how to conduct an electrical hazard assessment or how to select PPE. For guidance on compliance, you need to look to national consensus standards. NFPA is one of the foremost consensus standards for electrical safety. It covers employee protection from the electrical hazards of shock, arc flash and arc blasts.
NFPA Compliance Part I - Installation Safety Requirements
Covers safety requirements for the design and installation of electric conductors and equipment. Essential to the proper use of Part I of this standard is the understanding that it is not intended to be applied as a design, installation, modification, or construction standard for an electrical installation or system. Its content has been intentionally limited in comparison to the content of the NEC in order to apply to an electrical installation or system as part of an employee's workplace. This standard is compatible with corresponding provisions of the NEC, but is not intended to, nor can it, be used in lieu of the NEC.
Part 2 - Safety Related Work Practices
Covers electrical safety related work practices and procedures for employees who work on or near exposed energized electrical conductors or circuit parts. Electrical hazard includes arc flash. Relevant requirements include:
- Power must be proven to be off before performing work.
This includes:
- The safe interruption of the load and opening of the disconnect
- Visual verification/voltage testing to ensure deenergization
- The potential electrical hazard must be identified and documented
- Flash hazard analysis must be performed
- Flash protection boundaries must be determined
- Appropriate steps must be taken to protect persons working near live parts or within the flash protection boundary
- Personal Protective Equipment must be provided, based on the relevant incident energy exposure levels (cal/cm2)
- Only properly qualified persons shall be allowed to perform work
Part 3 - Safety Related Maintenance Requirements
Covers practical safety-related maintenance requirements for electrical equipment and installations in workplaces.
Part 4 - Safety Requirements for Special Equipment
Covers electrical safety installation requirements and safety-related work practices and procedures for employees who work on or near special electrical equipment such as electrolytic cells.
Preventing Arc Flash Incidents
Step 1. Perform Hazard Assessment and Create Warning Labels
The label is the first step. However, determining the arc-flash levels may change as routine maintenance and repair is performed. The level of arc-flash hazard of any piece of equipment depends on the level of arc-fault current and the time it takes to trip the nearest upstream over current protection device. In most cases, a local utility engineer can determine the fault current levels; however these fault current values may be based on the impedance of the transformer that serves the facility, and additional impedances upstream of the transformer can lower the number. If these additional impedances are not included in the calculations, then the incident energy levels may be under-estimated. Short-circuit current levels in electric utility systems are continuously changing as both electricians and maintenance workers replace over current devices, fuses and panel boards or upgrades are made to the system. Any of theses changes can have an effect on the arc-flash energy level, but may not be noted on the warning label.
Step 2. Provide Protective Clothing
The next step is to ensure that anyone working on equipment that might generate arc flash wear protective clothing, including fire retardant suits, gloves, face shield/goggles and other gear as provided by the standards.
Step 3. Equipment That Limits Exposure
Although no single piece of equipment can completely eliminate arc flash hazards, making it convenient to perform most routine maintenance tasks without directly accessing the equipment can significantly reduce the risk. Providing external plug-ins to equipment inside an enclosure is one approach. Properly designed and insulated panels that are wired to the appropriate equipment inside allows operators to change settings and monitor performance without opening the enclosure. With a traditional disconnect switch inside the main enclosure, live power is still present on the line side of the disconnect switch. Since live power is still being fed upstream to the disconnect switch on the panel, the threat of an arc flash incident remains. Another approach is to develop arc-resistant electrical cabinets designed to contain the arc energy and direct it away from personnel- - they cannot prevent an arc flash. "Arc-resistant" describes equipment designed to control arc flash exposure by extinguishing the arc, by controlling the spread of the arc or by channeling the arc pressure wave away from personnel. Arc-resistant designs represent enhanced safety technology and, therefore, an enhanced level of safety." The design redirects arc flash energy out relief vents at the top of the unit and away from personnel through an overhead plenum. These products have been successfully tested in accordance with ANSI C37.20.7: IEEE Guide for Testing Medium-Voltage Metal- Enclosed Switchgear for Internal Arcing Faults. During testing, cotton squares (similar to 4.5 oz/yard untreated T-shirt material) are mounted a meter from the MCC. Acceptance criteria require that none of the cotton indicators ignite during or following a test. To redirect the arc exhaust gases, specialized silicone coated, aluminum pressure relief vents on the unit's roof open to release the pressure. A plenum system above the enclosure channels the superheated gas and vaporized copper and steel to a safe and controlled location.
Standards Organizations and Arc Flash Protection
To protect operators, OSHA and NFPA 70E standards require a "flash protection boundary." OSHA has adopted the National Fire Protection Association's "70E Standards for Electric Safety in the Workplace" as an acceptable means of compliance to meet this requirement. Section 1910.333 of Subpart S states: "Safety-related work practices shall be employed to prevent electrical shock or other injuries resulting from either direct or indirect electrical contacts". Therefore companies should take great lengths to ensure that electrical workers are safe from arc-flash dangers.
References:
Organizations Involved In This Work
NFPA - The National Fire Protection Agency
The mission of the international nonprofit NFPA is to reduce the worldwide burden of fire and other hazards on the quality of life by providing and advocating consensus codes and standards, research, training, and education. NFPA membership totals more than 81,000 individuals from around the world and more than 80 national trade and professional organizations. Established in 1896, NFPA serves as the world's leading advocate of fire prevention and is an authoritative source on public safety. In fact, NFPA's 300 codes and standards influence every building, process, service, design, and installation in the United States, as well as many of those used in other countries. NFPA's focus on true consensus has helped the association's code-development process earn accreditation from the American National Standards Institute (ANSI).
OSHA - Occupational Safety & Health Administration
OSHA's mission is to send every worker home whole and healthy every day. Since the agency was established in 1971, workplace fatalities have been cut by 62 percent and occupational injury and illness rates have declined 40 percent. At the same time, U.S. employment has nearly doubled from 56 million workers at 3.5 million worksites to 115 million workers at nearly 7 million sites.
ASTM
ASTM International (Originally known as the American Society for Testing and Materials) is one of the largest voluntary standards development organizations in the world-a trusted source for technical standards for materials, products, systems, and services. Known for their high technical quality and market relevancy, ASTM International standards have an important role in the information infrastructure that guides design, manufacturing and trade in the global economy.
IEEE - IEEE Electrical Safety
A predominant area of standards activity within the IEEE-SA addresses technology and related safety needs for the power and energy industry and subsequent industry applications. A key component to electrical safety is for those working with electrical current and within environments using electrical current to be abreast of standards and regulations that include safety best practices. It is critical for employees to familiarize themselves with these documents and the organizations responsible for developing them. The IEEE, namely via its Color Books Standards for Industrial and Commercial Power Systems and the National Electrical Safety Code, as well as its Power Engineering standards, is a major developer of standards that directly or indirectly address electrical safety within specific applications or environments.
Additional Resource Links
NFPA 70B Recommended Practice for Electrical Equipment Maintenance, 2006 Edition NFPA Journal May/June 2007 Newsletter
Please visit us at www.electrophysics.com/wpnfpaupab
For more comprehensive White Papers visit our online Knowledge Center www.electrophysics.com/thermal-imaging
Electrophysics - IR Cameras for Thermography Professionals
373 Route 46, Fairfield, NJ 07004?Phone: 973-882-0211?Fax: 973-882-0997
- Related Articles
- Related Q&A
- Periodic Infrared Inspection Best Practices - Route Based Surveys
- Guidelines for Performing Infrared Inspections of Motor Control Centers
- Nfpa70e, Arc Flash and Safe and Efficient Thermography Practices
- Ir-cam Epm - 25 Thermography Ir Imaging Camera
- Testing Building Envelope Systems Using Infrared Thermal Imaging
- Infrared Thermography Revolutionizes Home Inspection Industry
- Locating Levels in Tanks and Silos Using Infrared Thermal Imaging
- Integrating Thermography With Your Cmms-eam Systems




Space Heater Hazards
By: Artie Megibben | 04/01/2010It’s wintertime. And that means hot apple cider, fuzzy earmuffs and a giant uptick in residential fires.
M is for Music, the Samsung M3310 Dual Slider
By: Simon Drew | 04/01/2010While this phone will not give users unlimited music access like the Nokia music phones nor does this phone have the same iconic feel of the iPhone; the Samsung M3310 is still a very impressive standalone music playing device that comes with its own high quality speaker.
Where Can You Pay For Portable MP3 Players?
By: Floyd P. Dietz | 04/01/2010Portable MP3 players and portable MP3 player recorders are becoming more and more popular by the day. In fact, you'd probably have a hard time finding anyone who didn't have one of these players. For that reason, retailers all across the world are stocking up so that anyone can buy portable MP3 players from them. You don't have to look far in order to buy a portable MP3 player that you may have your eyes on.
Tips to Use R4 DS Slots on Computers|Ishopvideogame
By: ishop videogame | 04/01/2010This article is aimed at teaching you to use R4 DS card in a correct way. Please do follow it before you use R4 DS card.
Knowing The 1gb Mp3 Player Review
By: Douglas M. Parks | 04/01/2010A lot of people tend to want to start small when they first start learning about a new system or electronic. Whether this is a gift for yourself or for someone dear to your heart, you may be worried about spending too much money on something that you know very little about. This is why it is so important to start small so that you are not spending an overload of money and also read up on the product as much as possible.
Hunting For The Best Waterproof MP3 Player
By: Kenneth D. Tafolla | 04/01/2010An MP3 player is an electronic device that is utilized for playing digital audio files. These audio files are in an MP3 format. Technically speaking this MP3 format is a form of lossy data compression. This simply means that the original music is compressed greatly which allows for less data to be used while still maintaining the integrity of the music.
Europe PV Inverter Market Expected to Exceed $3 Billion in Revenues by 2015
By: Bharat Book Bureau | 04/01/2010Bharatbook.com added a new report on "Europe PV Inverter Market Analysis and Forecasts to 2015" which gives the development and trends towards PV Inverter Market in Europe.
6 Tips to Distinguish Fake Nintendo DSi LL(XL) vs Clone Ones
By: ishop videogame | 04/01/2010There are some fake Nintendo DSi ll on the current market. This article is teaching you how to distinguish it.
The Three Primary Technologies for Night-time Video Surveillance
By: Josh White | 14/05/2009 | ElectronicsThe three primary technologies for night-time video surveillance are: low-light imaging, thermal imaging, and near-infrared illumination. Understanding the advantages and disadvantages of each technology will assure that a surveillance system delivers the desired performance at night.
Testing Building Envelope Systems Using Infrared Thermal Imaging
By: Josh White | 16/12/2008 | ElectronicsThe structures we live and work in are susceptible to quality and performance problems during construction and maintenance that can impact performance and may, in some cases, render them dangerous. Regardless of the building type involved, infrared thermography can provide remarkable, nondestructive information about construction details and building performance.
Guidelines for Performing Infrared Inspections of Motor Control Centers
By: Josh White | 16/12/2008 | ElectronicsWhether it's your first infrared inspection or you're a veteran with hundreds of surveys under your belt, it is important to realize that in order to successfully identify and analyze thermal anomalies, it is beneficial to understand the operation of the equipment under inspection. This paper will provide guidelines for inspecting the motor control center (MCC), identifying key components and potential problem areas, illustrating both common and not-so-common thermal anomalies.
Nfpa 70e and Its Impact on Thermographers
By: Josh White | 16/12/2008 | ElectronicsThere continues to be a great deal of activity surrounding the update to NFPA 70E scheduled to be published in October 2008. For the proposed 2008 edition of NFPA 70, National Electrical Code® (NEC®), the Technical Correlating Committee (TCC) received 3,668 proposals and 3,206 comments during the revision cycle. For those of us involved in working with energized electrical circuits the outcome of the new standards will likely impact how we do our job.
Nfpa70e, Arc Flash and Safe and Efficient Thermography Practices
By: Josh White | 16/12/2008 | ElectronicsEstimates indicate that 10-15 serious arc-flash incidents; those that result in burn injuries requiring treatment in a burn center, occur each day in the U.S., so it is not surprising that awareness of the hazards associated with arc flash continues to grow. Concerns about operator safety are causing inspectors of high voltage switchgear to adopt new practices and new equipment. We will examine the impact of new safety practices.
Periodic Infrared Inspection Best Practices - Route Based Surveys
By: Josh White | 16/12/2008 | ElectronicsAbstract Infrared thermographic inspection is an established PdM inspection modality. Recent advances in infrared camera platforms have created a new class of infrared imaging instrument which incorporates pen-based computing and application specific software into a powerful thermal inspection data logger with many traits similar to mature vibration data collection systems.
Locating Levels in Tanks and Silos Using Infrared Thermal Imaging
By: Josh White | 11/12/2008 | ElectronicsInstrumentation for locating levels in tanks and silos is often unreliable. The need for precise information about levels remains necessary, or even critical, in many instances. For example, in one situation a thermographer was employed to verify a liquid level in a large storage tank along the Gulf Coast prior to the arrival of a tanker ship.