Design of Local Exhaust Systems for Industrial Air Cleaning

Local exhaust ventilation systems are designed to capture airborne chemicals at the source of generation and remove contaminants from the work area. When a local exhaust system does its job your workers are healthy and productive. It usually consists of:

- hoods for capturing the contaminant

- ducts for transporting the contaminant

- air cleaner for removing contaminants from the air stream

- fan to create airflow in the system

- stack to discharge the air outside the workplace.

To design a Local Exhaust System we must know the:

* physical state of the chemical (Is it a dust, mist, fume, gas or vapor ?),

* chemical's toxicity and applicable exposure limits,

* physical properties of the chemical (Vapor pressure, boiling point, flash point),

* routes of worker exposure -- inhalation, ingestion, skin contact,

* how, where and when the chemical is used,

* how the worker does their job.

HOOD DESIGN

A well-designed hood is the most important component of an effective LEVS. The hood must be positioned so that it does not pull contaminated air through the worker's breathing zone. It should be easy to use and not interfere with the job that the worker is trying to do. It should be positioned as close to the point of contaminant generation as possible. The further it is from the point where the chemical is released into the air, the more airflow is required to capture the contaminant.

AIR VOLUME AND CAPTURE VELOCITY

The air volume (cubic feet per minute) that must be exhausted by LEVS is determined by the type of hood, the distance of the hood from the source of the contaminant and the velocity needed to capture the contaminant (Capture Velocity). Capture velocity for a hood is determined by the properties of the chemical and how it is being used. Examples of capture velocities are shown in Table 1.

MAKE UP AIR

Air will only be exhausted to the extent that air enters the workplace. If you don't provide make up air in the amount at least equal to the amount of air being exhausted, your LEVS will not work properly and the workplace will be very drafty, doors will be difficult to open, and furnaces, heaters or other combustion equipment may back draft.

TRANSPORT VELOCITY AND DUCT SIZE

Once a contaminant is captured by the hood it moves into the duct system. The velocity in the duct must be sufficient to transport the contaminant through the LEVS. The velocity in the duct necessary to carry the contaminant through the system is referred to as the transport velocity. The heavier the contaminant the higher the velocity needed for transport. Some examples of transport velocities for different contaminants are shown in Table 2. Once you know the airflow volume and transport velocity needed for a LEVS, the duct size can be calculated using the formula shown in Table 3.

sTREAMLINE AIR FLOW

Local exhaust systems should always use round ducts, because airflow is more uniform and streamlined, which makes the system more efficient and provides better transport for contaminants. The duct runs should be as straight as possible; curves should be smooth and gradual; and an elbow should have a radius of 2 to 2.5 times the duct diameter. Branch entries into the main duct should be at an angle of 45?; there should be no 90? entries. All changes in size should be smooth and gradual.

STACKS

A stack should discharge contaminated air vertically upward and away from the building. Stacks should be located as far from air intake units as possible to prevent reintroduction of contaminated air into the building. The top of the stack should be 1.3 to 2 times the building height above the ground. Avoid exhausting air out of the sides of buildings. The pressure of prevailing winds blowing into the exhaust can severely affect the performance of the LEVS.

FAN SELECTION

The fan you select for your LEVS should be based on the needs of the system. It should not only deliver the volume of air (in cubic feet per minute) necessary to capture the contaminant but be able to do so against the resistance to airflow in the system. The resistance to airflow is measured in inches of water and is usually referred to as static pressure losses. Static pressure losses in LOCAL EXHAUST SYSTEM are determined by the:

- size of the duct,

- roughness of the duct material,

- number and type of elbows, entries, and changes in size,

- type of air cleaner,

- type of hood,

- volume of air flowing in the system,

- stack design.
 
It should be clear from this list that a fan cannot possibly be selected successfully until the system has been designed.

SYSTEM INSTALLATION

Insist that you get a system installed as designed, with round ducts and smooth streamlined airflow. Since a rough duct increases static pressure losses and requires a larger fan, you should keep the use of a flexible duct, which is very rough, to a minimum. Use a flexible duct only where you need flexibility and use as little of it as possible.

Fans will operate more efficiently if they are installed with a length of straight duct entering and leaving the fan. A rule of thumb is to provide a straight run of duct at least six duct diameters long on the entrance side of the fan and at least two duct diameters long on the exit side. After installing the system, measure to ensure that the LEVS delivers the airflow volume and velocity that is needed to do the job.

For additional information please refer to http://nis-co.com/dustcollector/Index.html.

Oleg Tchetchel
Process Engineer
Canadian Air Systems
http://www.nis-co.com/fumeextractor/Index.html
http://www.nis-co.com/scrubber/Index.html

Oleg Tchetchel

Oleg Tchetchel Designer of Air Moving Systems Canadian Air Systems http://nis-co.com/contact/Index.html

Rate this Article: 0 / 5 stars - 0 vote(s)
Print Email Re-Publish

Add new Comment



Captcha

  • Latest Science Articles
  • More from Oleg Tchetchel

Basic Principles and Purity Determination by Differential Scanning Calorimetry

By: poongothai | 02/12/2009
Purity and quality are the major events in pharmaceutical sector. Heating rate, sample mass, particle size, atmosphere and calculation procedure involves mainly on the determination of purity of any pharmaceutical ingredient by means of melting point depression with differential scanning calorimetry.

RFID Technology For Laboratory Specimen Tracking

By: Arthor Pens | 02/12/2009
Specimen inventory control is often a costly, time-consuming process for modern laboratories. Using RFID tags for lab sample management prevents mistakes, improves patient safety and adds efficiency to laboratory operations. This article illustrates the benefits of automated sample labeling and tracking and provides guidance for implementing labeling systems that provide safe, accurate sample identification.

Microbiology Analysis of Drinking Water

By: Fereshteh Safarzadeh Markhali | 01/12/2009
Drinking water supplies are prone to contamination with sewage or other excreted matter may cause outbreaks of intestinal infections such as typhoid fever.

Three Most Under-Used Laser Procedures – Warts, Skin Stains and Scars

By: Andrew Wood | 01/12/2009
Laser procedures are gaining popularity with unprecedented momentum. Laser hair removal is among the fastest growing male cosmetic procedures, and is quickly eating into over $130 million that Australians spend on home depilation products every year. However, many people (customers and clinic owners included) don’t realize the breadth of applications that a single medical laser machine has.

Process Analytical Technology – Application of Near IR Spectroscopy in Pharmaceutical Processes

By: poongothai | 01/12/2009
Drug product manufacturing in pharmaceutical industries is generally controlled by testing products resulting from a process - finished product testing. Another innovative approach is process analytical technology (PAT) analytical testing is performed during the process. Process understanding is the basis for this innovative process control system.

What is the GHS Classification and Labeling regulation?

By: Editor123 | 01/12/2009
GHS (Globally Harmonized System) has been developed in order to protect human health and the environment by providing an internationally comprehensive system for hazard communication.

The Process of Metal Working

By: Ryan Fyfe | 01/12/2009
Metalworking is the process of working with metals to create a diverse range of products, from the hulls of ships to engagement rings. There are many reasons to practice metalworking. Metalworking can be used for experimentation, to create works ..

How to Perform Bacteria Identification Using Gas Chromatography of Fatty Acid Methyl Ester?

By: Fabio Pacheco | 30/11/2009
As stated in my previous article “The Importance of Bacteria Identification in Clean Rooms”, we are supposed to identify the flora obtained from environment samples, and it is not limited to clean room environments. In this article, I am going to focus on bacteria identification solely.

Air Curtains for Large Buildings Doors

By: Oleg Tchetchel | 17/09/2009 | Education
The idea of having an invisible barrier across the doorway to enable unimpeded access yet effectively prevent temperature flow, dust, odours and insects to cross, is appealing in itself but add to this the cost-saving in reducing energy use and the idea becomes more compelling, especially as air curtains are relatively inexpensive items. Appropriate for industrial applications Keeping warm air out of insulated cold stores or refrigerated facilities

Design of Local Exhaust Systems for Industrial Air Cleaning

By: Oleg Tchetchel | 15/09/2009 | Science
Local exhaust ventilation systems are designed to capture airborne chemicals at the source of generation and remove contaminants from the work area. When a local exhaust system does its job your workers are healthy and productive.

Heavy Duty Industrial Process Air Curtains

By: Oleg Tchetchel | 14/09/2009 | Health
An air door or air curtain is a device used for separating two spaces from each other, usually at the exterior entrance. The most common configuration for air curtains is a downward-facing blower fan mounted over an opening. Normally this opening is an entrance to a building, and the air curtain is intended to help keep flying insects out by creating forceful turbulence. It also helps keep outside air out, avoiding cold drafts by mixing-in warm air from the air curtain.

Air Blowoff Systems for Industry

By: Oleg Tchetchel | 11/09/2009 | Business Ideas
Blower and fan units used in tank, blender, and conveyor tube drying can reduce drying time by an average of 50% compared with natural air drying. They are almost always a direct-drive design in order to minimize size and cost. However, an in-line electric heater must be added, and this ultimately raises both the cost and total power consumption. The final assembly still must be compact enough to mount on a portable cart to easily service multiple mixers, and this portability requirement limits

Air Curtains by Canadian Air Systems

By: Oleg Tchetchel | 10/09/2009 | Causes & Organizations
Air curtains are widely accepted across North America and Europe as a standard fitment in public buildings, retail stores and industrial applications such as coolers, freezers and cold storage facilities. Air curtains are generally associated with retaining heat energy in cold climates, and the energy savings are substantial.

Air Make-Up by Industrial Air Handling Units

By: Oleg Tchetchel | 15/06/2009 | Health
Makeup air is vitally important to the health and welfare of a building and its occupants. If the proper amount of makeup air is not introduced into a space, consequences can range from exterior doors that are hard to open or close, to buildups of carbon monoxide in the space, to fume hoods that don't actually control the contaminants they were intended to control.

Industrial Direct-Fired Air Handling Units

By: Oleg Tchetchel | 12/06/2009 | International Business
Direct-fired units utilize air that will be sent to the heated space for combustion without use of a heat exchanger. The products of combustion are mixed directly with large volumes of outdoor air. Such mixing is considered safe because of the high dilution ratio.

Industrial Air Handling Units for Air Temperature Control

By: Oleg Tchetchel | 04/06/2009 | Kitchens
Direct Gas-Fired Heating Systems may be built in a number of configurations. They may be curb mounted as horizontal rooftop systems with down or horizontal discharge or in a vertical configuration for mounting on a pad outside of a building, with air ducted to the interior. They may also be located inside a building, suspended from hangers or mounted on support steel. Various manufacturers can supply any physical configuration required.

Submit Your Articles Free: Signup
Article Categories




Use of this web site constitutes acceptance of the Terms Of Use and Privacy Policy | User published content is licensed under a Creative Commons License.
Copyright © 2005-2008 Free Articles by ArticlesBase.com, All rights reserved. (0.30, 6, w1)